mail@mabbaz.com Abu Dhabi, UAE

BMS · Analytics · Data Quality

Handling Sensor Units and Scaling in BMS Analytics

A reading travels from a physical quantity through a signal, a scaling, a protocol and a store before anybody analyses it, and every one of those steps can change what the number means. Analytics across a mixed estate fails on this far more often than on anything algorithmic. These are the places it goes wrong and the conventions that prevent it.

Muhammad Abbas October 27, 2026 ~12 min read

Build an analytics rule for one air handling unit and it works. Apply it across forty units from three manufacturers installed over fifteen years and it produces nonsense on a third of them. The usual diagnosis is that the rule needs tuning. The actual cause, most of the time, is that the same physical quantity is represented differently on different units, and the rule is comparing values that are not in the same units.

The message up front: pick one canonical unit per quantity for the whole estate, convert on the way in, and store the original alongside the converted value so the conversion is auditable. Capture the unit from the device rather than inferring it from a name. And resist the urge to normalise silently: a conversion that cannot be traced is indistinguishable from a bug, and analytics built on untraceable conversions cannot be debugged when it eventually disagrees with the building.

1. Where the meaning can change

Five places, each capable of altering the number without altering anything visible.

  • The sensor. Its range and output characteristic determine what the raw signal means. A transmitter ranged for one span fitted where another was specified produces readings wrong in proportion.
  • The controller input. Raw signal converted to an engineering value by a scaling configuration. A scaling that does not match the device fitted is the most common single error, and it is covered from the commissioning side in BMS points lists and field devices.
  • The object's declared unit. What the controller says the value is in, which may or may not match what the scaling actually produces. The property exists and is described in BACnet objects and addressing.
  • The integration. Any conversion applied in a gateway, middleware or collector, which may be configured per point and documented nowhere.
  • The analytics or reporting layer. A final conversion, often applied because somebody noticed a value looked wrong and compensated rather than tracing the cause.

Each layer is defensible on its own. The failure is cumulative: a conversion applied twice, or in two layers that each assume the other did not, produces a value that is internally consistent and wrong.

2. The specific errors that recur

Error How it presents How to catch it
Prefix mismatchValues out by a factor of a thousand, usually on pressure or energyMagnitude check against a physically plausible band per quantity
Mixed temperature scalesPlausible numbers that are simply a different scale; differences and absolute values behave differently under conversionRange check, and never assume a scale from a numeric range alone
Absolute versus differentialA differential pressure reported as absolute, or the reverse. Both plausible, both wrong in a ruleDeclared quantity type on the point, not inferred from the name
Percentage versus fractionValues out by a factor of a hundred on anything expressed as a proportionRange check, which catches this cleanly
Scaling not matching the fitted deviceA reading that tracks the real quantity but with a wrong gain or offset. Hardest to seeComparison against a reference instrument, or against a related point
Double conversionInternally consistent, wrong by the factorOnly an audit of where conversions are applied. No data check finds this
Sign conventionFlow or energy flowing the opposite way to expectationCross-point consistency against a known direction
Convert once, on the way in, and keep the original

Store three things per reading: the value as the device reported it, the unit as the device declared it, and the value converted to your canonical unit. The storage cost is trivial and it makes every conversion auditable, reversible and diffable. The alternative, converting in each consumer, guarantees that two reports eventually disagree and nobody can establish which is right. It also means that when a scaling error is found and corrected at the controller, you can see exactly which historical rows were affected rather than guessing at a date.

3. A canonical unit per quantity

The decision is less about which unit than about having exactly one, declared, for the whole estate.

  • One unit per physical quantity, written down, applied without exception. Where an estate spans regions with different conventions, convert at presentation rather than storing both.
  • Distinguish quantity types that share a unit. An absolute pressure and a differential pressure may both be reported in the same unit and must not be compared. The quantity type is a separate field from the unit.
  • Record the sign convention for anything directional, because it is a convention rather than a property of the measurement.
  • Treat dimensionless values carefully. Percentages, ratios and indices need a declared basis, because the number alone does not carry it.
  • Store the canonical unit against the point in the register described in the BMS point dictionary, with effective dates, so a change of convention is visible in the history.

Meter points carry additional semantics beyond units, principally whether they report a rate or a quantity and whether that quantity is cumulative, and those are handled separately in validating meter units before energy reports.

4. Why analytics is where this surfaces

A single operator looking at a single graphic tolerates inconsistency easily, because they know their building and mentally adjust. Three properties of analytics remove that tolerance.

  • Rules are written once and applied to many points. A threshold that is correct in one unit is wrong by a factor in another, and the rule has no way to know.
  • Comparison across assets is the point. Benchmarking forty units against each other is meaningless if they are not in the same units, and the output looks like genuine variation between units rather than a data defect.
  • Derived quantities multiply the error. Anything computed from two readings inherits both their unit assumptions, so an efficiency or a load calculation can be wrong in ways neither input reveals.
  • Models learn the inconsistency. A statistical approach trained across mixed units will treat the unit difference as a real pattern, which is one of the prerequisites discussed in anomaly detection data readiness.

5. Finding the problems in existing data

  • Group by quantity and compare distributions across points. Points measuring the same thing should have broadly similar ranges. Those sitting a clean factor away from the rest are the unit errors, and this is the single most productive check.
  • Plausibility bands per quantity. Not alarm limits but physical possibility. Anything outside is a data problem whatever the plant is doing.
  • Compare the declared unit against the observed range. A point declaring one unit while reporting values typical of another is self-evidently mis-scaled.
  • Cross-point relationships. Values that must bear a physical relationship to each other, and do not, indicate one of them is in the wrong units. The consistency-check approach is in BACnet data quality flags.
  • Audit where conversions are configured. The only way to find double conversion, and it is a documentation exercise rather than a query.

6. Preventing it on new work

  • Require declared units in the points schedule, per point, as a deliverable rather than an optional column.
  • Require the scaling configuration to be documented against the device actually fitted, with make, model and range.
  • Verify units during acceptance, by comparing the declared unit against the object property and against the observed range, which is part of the set in the BACnet integration acceptance test checklist.
  • State where conversion happens in the integration design, once, and require every other layer to pass values through unmodified.
  • Make a unit or scaling change a recorded event with effective dates, because it creates a step in the history exactly as an instrument change does.
Limits

No specific units are recommended as canonical, and no plausibility bands, ranges or conversion factors are given, because the right choices depend on your estate, your region and what the data is used for, and a borrowed band would either flag everything or nothing. Take ranges from the equipment and the design. Whether a particular scaling is correct for a particular device, and whether an out-of-band reading represents a data problem or a real condition, is engineering judgement for a controls or instrumentation engineer with the plant in front of them. This article covers the data model and the conventions, which is my own domain.

The idea to walk away with

Units are not presentation, they are part of the value. A number stored without its unit is incomplete, and a number converted without a record of the conversion is unverifiable.

So capture the unit from the device, convert once on ingestion to a canonical unit declared for the whole estate, keep the original alongside, and record the quantity type and sign convention separately because the unit alone does not carry them. Everything analytical becomes possible after that and remains unreliable before it.

Final thoughts

The most productive hour available here is a distribution comparison: group every point by the quantity it measures and plot the ranges side by side. Unit errors do not hide in that view, because they sit a clean factor away from their peers.

It is also the exercise that tends to change people's confidence in their own data, because the scale of the inconsistency across a mixed estate is usually larger than expected and entirely fixable once it is visible.

Disclosure

Alongside advisory work I also build a CMMS and CAFM platform, so I have a commercial interest in this category. Nothing above is a recommendation for it, and no vendor named here has paid for inclusion or had any editorial input. Weigh the analysis accordingly.

Analytics producing nonsense on some assets?

Independent review of unit capture and conversion: finding the mis-scaled points, choosing canonical units, auditing where conversions are applied, and getting the record into the point register. 22+ years across CMMS, CAFM, EAM and ERP implementations.

Book a conversation

Related reading: Validating meter units, BACnet data quality flags, BMS point dictionary, BMS points lists and field devices, Sensor replacement and BMS history, BACnet objects and addressing.

Muhammad Abbas

CMMS / CAFM Manager & Independent Advisor · 22+ years across enterprise CMMS, EAM, CAFM and ERP implementations in utilities, oil and gas, manufacturing, government and facility operations.

Work with me
MAbbaz.com
© MAbbaz.com